Product Details:
Payment & Shipping Terms:
|
Voltage: | 3* 230V/400V | Current: | 3*5(60)A |
---|---|---|---|
Frequency: | 50Hz/60Hz | Accuracy Class: | Active: 1.0 Reactive: 2.0 |
Pulse Constant: | 3*400imp/kwh | Communication Mode: | Lora-RF Module |
Data Storage Period: | 10 Years | Name: | Three Phase Smart Meter |
Display: | 6+2; 5+1 | Power Consumption: | Less Than 2.0W |
High Light: | Smart Water Meter,Lora Gas Meter |
4 Programmed Lora Smart Meter Three Phase Multi Channels Energy Meter with Lora-RF Module
Main Features:
● Metering
● Loadprofile
At least 4 loadprofile channels,Recordat least 490days data when time interval is 30 minutes
● Optical port interface
Support IEC62056-21protocol, 1200bps for communication
● RS-485 serial interface
SupportIEC62056(DLMS/COSEM) protocol, 2400bps for communication
● LCD display
Number of digits value field Up to 8
Digit size 6x14.5mm
● Inputs and outputs
Optical test outputs active energy and reactive energy
● Communication modules(optional)
GPRS module:EGSM900/DCS1800 dual-band,support GSM/GPRSphase2/2+ protocol
PLC module: according to Technology Standards of SSC163X ,centerfrequency 270K, FSK modulate technolgy
● Energy Measurement
Total and time-sharing forward active & reactiveenergy measurement
Total and time-sharing reverse active & reactive energymeasurement
Total forward & reverse apparent energy measurement
Save last one to sixteen months energy data
● Max. Demand Measurement
Measure total and time-sharing forward active &reactive maximum demand and time of occurred
Measure total and time-sharing reverse active &reactive maximum demand and time of occurred
Measure total forward & reverse apparent maximumdemand and time of occurred
● Real Time Measurement
Real-time measurement of the phase voltage, current,total active power,
reactive power, apparent power, total power factor, powergrid frequency
● TOU
4tariffs, 100holidays, 14season‐tables, 8time zone‐tables, each table onmaximum 14 time zones
● Event Log
The last 10 records of following events:Power-down,Programing, Cover opening, Terminal cover opening, Reverse power,
PhaseFail.the records include data and time
Main Parameter:
Item | Specification | |
Reference Current | 1.5(6)A 5(40)A 5(60)A 15(60)A 20(100)A | |
Reference Voltage | 3×220V/380V | |
Dimension (mm) | 290×170×85 | |
Working Voltage Range | 0.8Un~1.15Un | |
Maximum Working Voltage | 0.7Un~1.2Un | |
Working Temperature | -25℃~+60℃ | |
Maximum Working Temperature | -40℃~+70℃ | |
Accuracy | Active 1.0 | Reactive 2.0 |
Relative Humidity | ≤95% | ||||||
Frequency | (45~60)Hz | ||||||
Start Present | Direct Mode 0.004In; | ||||||
CT Mode: 0.002In | |||||||
Consumption | <1.5W,10VA |
Factory setting subject to nameplate | ||||||||
For 1.5(6)A meter: Active | 6400imp/kW·h | |||||||
Reactive | 6400imp/kvar·h | |||||||
For 5(40)A meter: Active | 600imp/kW·h | |||||||
Constant | Reactive | 600imp/kvar·h | ||||||
For 5(60)A /15(60)A meter: Active | 400imp/kW·h | |||||||
Reactive | 400imp/kvar·h | |||||||
For 20(100)A | meter: | Active | 300imp/kW·h | |||||
Reactive | 300imp/kvar·h | |||||||
Pulse Width | (80±20)ms |
1) One device cater to various demand for smart metering
2) Cost saving and scalable setup
3) Time of Use multi-rate for flexible contractual control
4) Easy to install and low inventory
5) Fraud detection
6) Flexible setting for power limit, tariff, repayment policy
7) IP 54 rated
Why Choose Us
* Professional manufacturer for more than 15 years.
* Highly experienced production team in RADARKING factory work-shop.
* QC Systerm: Quality controlled on all production lines, and QC inspectors work independently from the production line.
* Good quality production with quick delivery.
* Accepted OEM/ODM.
* Accepted small MOQ.
* Factory certification: ISO9001, 14000, STS
Contact Person: Mrs. Ada Yang
Tel: 86 15623095278
Fax: 86-27-84967521